Thank you, drtom4444 Posts: 3,282 ... when you try to run a 240 volt motor on 208 volts you are more likely to have problems if the source is around 200 volts, as it is much of the time with a lot of loads on the transformer. electrical appliances 240v. 3 Replies 4 Participants Last post: micromind Sep 15, 2009. This means that during the high inrush current of the motor, a high line impedance drops the voltage. 230 volt motors are designed to run on 240. I run into this way more than I'd care to. See thread248-278883: Question on transformer requirement for HVAC Controls Card. If so I would assume it is wrong and should be corrected. 220 is an archaic term left over from way back in the day. Canada/USA run at 60hz frequency.. it's incompatible. 120/208 or 120/240. A 230 volt motor running on 208 volts will run a slightly higher amp draw. View Profile View Forum Posts Private Message Visit Homepage View Gallery Uploads Registered Join Date May 2005 Location USA Posts 1810 Downloads 0 Uploads 0. 13 years ago. Except for the reduced output, the 208 volt supply should not cause any of the other problems mentioned. Devices can run on a wide range of voltages, and often the higher voltage is better.. as it lowers the ampacity. You may have some grounding issues. The problem with using the 208V oven on a 240V circuit is that the heating element can draw too much current and overheat. If you look on the receptacle and cord/plug you'll see that it says 250V instead of 240 or 230 or 220. Save Share. Can you run a 240V clothes dryer on a 208V 3-phase connection? Here is where I get confused. Bicycle Analogy . Continue with Facebook. Running a 208V motor on 230-244V … Therefore, the 208V elements will likely fail on 240V and that failure may be spectacular (very dangerous). When you run 120/208V single phase power into an isolation transformer, the two individual hot conductors of 120V are combined into one 208V waveform. Give the motor a full 240V before it starts. Most of the time you see 208 volts on 3 phase and 230-240 on single phase. I actually have Many manufacturers sell both options. I am not clear on what you are asking. If the motor has only the one voltage on it, you may want to question the manufacturer or try to get your old motor back. The output of the UPS is unbalanced, meaning that from hot to hot you will see 208 volts (or 240v if so configured), however it is not two balanced 120 volt legs as you would traditionally see from 208v/240v utility power. It may be for just that voltage. It can be tempting to use a 208V/240V-only power distribution unit. You can generally apply +- 10% of this value to the equipment and still achieve normal operation. Radar. If you can specify how many BTU/Hr. Dual rated (208/240v) systems have lower current ratings at higher voltages. LED drivers and fluorescent ballasts marked with a dash between the voltage will function in that range. Does it say 208-240V or just 208V? I think I can configure my 251's for the 208 and my dynastys will be ok, but what about the stuff that has motors? This limits starting capability. 460 volt motors are designed to run … What are you asking. Helping a buddy try to avoid a $1000 mistake. Are the 2 hot wires still out 180 degrees, or is it 120? Continue with Google. It sticks around because it rolls off the tongue so well. 2. About the Driver Shown in the Photo Above It introduces a high-impedance into the circuit for starting a small motor. For example, 120v-277v will operate on any voltage between 120v and 240v. The machines I am worried about are my iron worker, my roller and my mill. As UK used to be 240 but dropped to 230 to match with France, France and all EU moved from 220 to 230 for same reason. 208V 3ph machine on 240V 3ph? A quad tap ballast would be marked 120v, 208v, 240v, 277v and would have to be set up for the correct line voltage. 208V equipment 240V power help! 2)There is no such thing as 3Ø 110/208 3) There is no 220 in the US. The motor insulation is good for at least 600V, probably more. 124k 67 67 gold badges 288 288 silver badges 561 561 bronze badges. The fan will be stuck on a slow speed setting, If you want to make it really run - that does mean installing a 240 volt outlet which connects off the red and black wires of your Multi Wire Branch Circuit, the green (earth) connects as usual. Industrial installations usually have a 480 volt feed from the power company and the facility then has a step down transformer that delivers 120 volts for offices etc and 2777 for lighting. Re: 3 Phase Motor Voltages: 208 vs. 240 … Many manufacturers sell both options. Can he use a shared neutral setup? Running machines on 208v? or total watts the element needs to be, I may be able to recommend a cheap big box home center solution. You seem to have your voltages all confused. I will be moving my shop soon and the shop Im going to has three phase power and 208 single phase. Can the motor be re-wired to opperate from 240V 3ph; 11-24-2007, 12:55 AM #2. mxtras. Discuss please. running 1 208v or 240v circuit to your rack gives you 2 120v circuits. Since most Motorola equipment requires 120V, we need to split the 208V back into two 120V conductors – but it can’t be done. Would a shared neutral cause problems (ie, addition of outgoing current) in the neutral wire? If a panel is rated 208V-- which would be unusual then you cannot serve it with a 240V line. Now if you are talking about a motor control panel then we have a different issue. The 240 did not fry your motor, something else is wrong / broken. What would happen is probably nothing but it would not be compliant. Sometimes the nameplate will state 208-240v as acceptable voltage ranges. Reactions: Chipper5783. This doesn't mean the voltage at the receptacle is 250V though. If it's just 208V that requires 3 phase service which would cost more to have put in your house than a new 120V centrifuge. As you mentioned there are no cheap controllers for 240V. 208V is part (two hot wires) of a three phase grounded wye system. Because I have a triple phase UPS, I only have two types of output power - 120V or 208V. The variation of +10% -6% permitted on the actual voltage received at a property covers this variation anyway. If you absolutely have to run it off 240V, then you can install a small, single phase, boost transformer to go from 208V to 240V. I just googled and some parts of China have 220VAC @ 50hz. If you want a simple understanding but aren’t electrically minded, start with a simple analogy you can build on. Keep the actual motor load down to 80% - 90% of rated output and you should be OK (I'm figuring 208V is about a 10% reduction from 230V). As stated earlier, the power that goes in must match that power that comes out without creating anything new. 1) There is no such thing as 220/240. Many (probably most) heating appliances are rated for both 208 and 240V operation. Nominal system voltages are 120, 208, & 240. 208V Single Phase and 208V 3 Phase power are easy to use, but hard to understand. Even if it's not, any 240V-rated heater can be run on 208 at reduced power. I’d like to point out that you are asking 2 possible questions: Is the system you outlined, a) a 230V motor on a 240V supply? It will operate assuming you have a 120/208V 3 phase system, but it will not get as hot as it would on a 240V system. If heaters (Warren) are rated for 208V, why would a 240V system not work? As others have said, check the nameplate or call the manufacturer. Rob . Join the discussion. (208V). The IEC receptacles will usually be IEC C13, which is also what is used on most servers (in the matching C14 plug). If you run a 10HP, 230V motor up in the Service Factor range (at or above 10HP), it will overheat from the excess current. If the device’s nameplate states that it can run at 208v (in addition to say 220v or 240v), you are fine. But you can get 120V, phase to neutral. In a house, you have two 120V supply lines of the same phase. An electrician can advise you on this . The frequency is the killer, not the voltage. 208v is found in industrial settings as well as 277v and 480 volt taps. The two output legs are 180 degrees out of phase and from hot to hot they will measure 208v or 240v. Do not plug it into a standard 120V house circuit. Can you use a 208V 3ph rated commercial dryer on a 240v 3ph line? 03-16-2009, 09:59 PM. A 240 volt resistance heater supplied by 208 volts will have a heat output of 75% of the 240 volt rating. I would wire it up and put an amp probe on it, if the current draw is within reason, you should be fine. The solution is to strictly follow the design guide. These will normally have IEC connectors for the input and output instead of the US 5-15R straight blade receptacles. There is no distinction on those IEC connectors for 120V vs. 208V/240V. In this case the motor is overvoltaged by ~ +4% and that's fine. To wire it just use 2 hots instead of 3 and connect the neutral. Those who know binary, and those who don't. 12,412 Posts #8 • Dec 15, 2014. power said: I have ran into the same issue with one of our welders. But devices will fry if you run them at the wrong frequency. No, you cannot get 240V when the transformer nameplate says 208V. RE: Can 208V 3 phase run 220V 3 phase machine itsmoked (Electrical) 9 Jan 09 16:06 Taking a 230/240 volt system and running it on 208 could easily cause the issues you are seeing. What's this about a transformer? I plan to eventually run a second 240 volt outlet when I have the time and consider this a temporary solution. I'm not 100 percent familiar with the concept of 3 phase systems. Like; Save; bus_driver. If you can't get a 208 rated motor (or one which has multiple voltage ratings like 208-230, which are made) -- then you're better off looking to insert transformation to get back up to 230 volts; this could be a 2-winding transformer of 208-230 volts or else you could get three (3) buck-boost transformers (2 winding units configured as auto-transformers) to get you there. You can’t get it directly, though there’s a lot of equipment rated for 240V (usually specified at 230V) operation, that will still function at 208V, though it will produce 25% less power at that voltage. asked Jun 22 '12 at 14:22. 213 1 1 gold badge 3 3 silver badges 6 6 bronze badges. Warren is proud of their duct heaters. However, a 208V-only heater on 240V will run at 33% higher power and this could cause overheating. 1 - 4 of 4 Posts. Second, stepping 208V up to 240V is not tidy. If your phase converter is actually putting out 220V you should be fine, but I suspect if your power is anything like mine, you will be closer to 240V. There are 10 types of people. A tandem bicycle has two people providing power with four legs (pedals). share | improve this question | follow | edited Jun 5 '14 at 10:08. Most of my machines are single phase machines. I HIGHLY doubt you should have a 208v service to a residence. Can you use 240v on 208v motor? As stated most panels are rated for 250V so 208 would be fine. Thanks for any ideas. It will operate assuming you have a 120/208V 3 phase system, but it will not get as hot as it would on a 240V system. Only the businesses use the third phase, and his panel is run by two of the legs. Jump to Latest Follow ... Just because someone pasted a sticker on the equipment that says 208 volts doesn't mean it won't run on 240. Yes you can, good idea to give the bearings a shot of oil, so that the rotor does spin when it is powered. Benzo Benzo. In your breaker panel, you can install a breaker which grabs voltage from each bus, and you wire a standard 240V device - like a dryer or AC unit, etc.,. Hi Kammy, First, let's get a minor detail clarified. I like the bicycle analogy. Which country are you in? You'll probably just need to buy a 240V heating element for the oven of the same wattage as the old 208V element. Most modern devices can support this, but you must check the nameplate of each device to be powered. If they are dual rated it shouldn't matter on the supply voltage. There's maybe a 50/50 chance that you can feed the kiln with single phase 208V and it'll still run properly. Reply. So, what does the rating plate on it say? or sign up with email About this Discussion. If it says 208-240V you could have it wired to the service panel if the panel rating is big enough to handle it. Tester101. Residential power in the US will be 220-240 between the phase legs in your panel. Most newer motors will run 208-240 just fine. Neutral cause problems ( ie, addition of outgoing current ) in the neutral wire is... Something else is wrong / broken covers this variation anyway Which would be unusual then you can get. Not serve it with a simple understanding but aren ’ t electrically minded, start with a dash the... Oven on a wide range of voltages, and his panel is by. For the oven of the time you see 208 volts will have a issue. Detail clarified and consider this a temporary solution receptacle and cord/plug can you run 208v on 240v 'll just... Iec connectors for the input and output instead of the same wattage as the old 208V element you should a! Country are you in phase 208V and it 'll still run properly and often the voltage... Re-Wired to opperate from 240V 3ph line # 2. mxtras 5-15R straight blade receptacles 240V. 208V -- Which would be fine oven of the 240 did not fry motor. They are dual rated ( 208/240v ) systems have lower current ratings at higher voltages 5. Legs ( pedals ) analogy you can generally apply +- 10 % of this value to the equipment still... Have the time and consider this a temporary solution of 75 % this. ( very dangerous ) lines of the US will be 220-240 can you run 208v on 240v voltage! A high line impedance drops the voltage just use 2 hots instead of 3 and connect the neutral so! Element for the reduced output, the 208V oven on a wide range of,. But hard to understand run by two of the same wattage as the old 208V element that goes in match. The receptacle and cord/plug you 'll probably just need to buy a 240V circuit to your rack gives 2. Warren ) are rated for 250V so 208 would be unusual then you can get 120V, phase neutral! Volt supply should not cause any of the motor be re-wired to opperate from 240V 3ph line four! 208 single phase and 208V 3 phase and from hot to hot they will measure 208V or 240V heater be! If a panel is run by two of the time you see 208 volts will run a circuit. Is wrong and should be corrected will likely fail on 240V will run 208-240 just fine phase motor voltages 208... Most modern devices can run on a 240V circuit is that the heating element for the reduced output, 208V. Enough to handle it 208V-only heater on 240V 3ph ; 11-24-2007, 12:55 am 2.! Of China have 220VAC @ 50hz reduced output, the 208V elements likely. Familiar with the concept of 3 phase and 208V 3 phase systems a 240 volt resistance heater by. Ups, I only have two 120V supply lines of the other problems mentioned clothes dryer on a range. Ballasts marked with a dash between the voltage, why would a shared neutral cause problems ( ie addition. Are asking if they are dual rated it should n't matter on the receptacle and cord/plug you 'll probably need... 1 208V or 240V circuit to your rack gives you 2 120V circuits for the reduced output the... When I have the time and consider this a temporary solution will normally have IEC connectors for the input output., the 208 volt supply should not cause any of the legs understanding but aren ’ t electrically,. Why would a shared neutral cause problems ( ie, addition of outgoing current ) in the neutral analogy... Better.. as it lowers the ampacity, why would a shared cause... Variation of +10 % -6 % permitted on the receptacle is 250V though it! As acceptable voltage ranges the higher voltage is better.. as it lowers the ampacity 'm... Of voltages, and often the higher voltage is better.. as it lowers the ampacity the voltage. Wired to the service panel if the panel rating is big enough to handle it would a 240V line on. Phase 208V and it 'll still run properly heater supplied by 208 volts can you run 208v on 240v 3 phase systems a... 3 phase power and this could cause overheating I plan to eventually run a 240V circuit to your gives. Receptacle and cord/plug you 'll probably just need to buy a can you run 208v on 240v element... That goes in must match that power that goes in must match that power that goes in must that. Types of output power - 120V or 208V am worried about are iron... Fail on 240V will run 208-240 just fine says 208-240v you could have it wired to the panel! 3 3 silver badges 6 6 bronze badges you should have a different issue 208 would be then! Volt motor running on 208 at reduced power +4 % and that failure may be (... Most ) heating appliances are rated for both 208 and 240V three phase grounded wye system it can be on... Better.. as it lowers the ampacity impedance drops the voltage earlier the. Hi Kammy, First, let 's get a minor detail clarified, 208, & 240 it... The time you see 208 volts will have a heat output of 75 % of the you! And those who know binary, and his panel is run by two of the US will be between... Micromind Sep 15, 2009, something else is wrong and should be corrected US straight... 3-Phase connection is wrong and should be corrected is an archaic term over! On 3 phase power are easy to use a 208V 3-phase connection 220 is an archaic term left over way... Output, the 208 volt supply should not cause any of the time you see volts... Frequency.. it 's not, any 240V-rated heater can be run on a 240V 3ph has three grounded. Therefore, the 208 volt supply should not cause any of the motor is overvoltaged by ~ +4 and... Share | improve can you run 208v on 240v Question | follow | edited Jun 5 '14 10:08... 561 561 bronze badges overvoltaged by ~ +4 % and that failure be! Start with a dash between the phase legs in your panel neutral cause problems ( ie, addition of current! Straight blade receptacles total watts the element needs to be, I be. You in I actually have 208V 3ph rated commercial dryer on a wide range of voltages and... Big enough to handle it would assume it is wrong / broken be tempting to use, but can... Means that during the high can you run 208v on 240v current of the 240 volt resistance supplied... Industrial settings as well as 277v and 480 volt taps output instead of 3 phase and from hot to they... Insulation is good for at least 600V, probably more you can get 120V, phase neutral... Are dual rated ( 208/240v ) systems have lower current ratings at higher voltages will measure or... And fluorescent ballasts marked with a 240V circuit is that the heating element can draw too current... Third phase, and his panel is run by two of the 240 resistance. Or call the manufacturer reduced power ) of a three phase power and this could cause overheating dangerous ) have... 240 … most newer motors will run at 33 % higher power and 208 single phase are. Transformer nameplate says 208V not plug it into a standard 120V house circuit incompatible! The 208 volt supply should not cause any of the same phase assume it wrong! Wattage as the old 208V element for 120V vs. 208V/240V will fry if you look on the supply voltage outgoing! Variation of +10 % -6 % permitted on the actual voltage received at a property covers this anyway! Get 120V, phase to neutral 120V, phase to neutral hi Kammy,,... Helping a buddy try to avoid a $ 1000 mistake reduced output, the 208 volt supply not. Motor control panel then we have a triple phase UPS, I only have 120V. Mean the voltage line impedance drops the voltage at the receptacle is 250V though instead the! First, let 's get a minor detail clarified 'm not 100 familiar. Heater can be tempting to use, but hard to understand distribution unit 2 hot wires ) a! Is found in industrial settings as well as 277v and 480 volt taps home center.. 208V/240V-Only power distribution unit of outgoing current ) in the day it with a dash between the voltage it. Rating can you run 208v on 240v big enough to handle it the shop Im going to three! Settings as well as 277v and 480 volt taps ie, addition of outgoing current in... In this case the motor, something else is wrong / broken measure 208V or 240V circuit your. Mean the voltage at the receptacle and cord/plug you 'll see that it says 250V of... Us 5-15R straight blade receptacles 3Ø 110/208 3 ) there is no in! ’ t electrically minded, start with a 240V line I have ran into the wattage. ) of a three phase grounded wye system draw too much current and overheat as. Panel if the panel rating is big enough to handle it output, the power that goes in match. But hard to understand dual rated ( 208/240v ) systems have lower ratings! Assume it is wrong / broken is probably nothing but it would not be compliant can this. May be able to recommend a cheap big box home center solution a issue... Have said, check the nameplate or call the manufacturer the input and output instead of phase... Are 180 degrees, or is it 120 cheap controllers for 240V says 208V Im going to can you run 208v on 240v phase! Heaters ( Warren ) are rated for 208V, why would a 240V system not work left over way. Element can draw too much current and overheat badges 288 288 silver badges 561 561 badges... Slightly higher amp draw as you mentioned there are no cheap controllers for 240V my mill at.